romex junction box in attic reddit As everyone mentioned you need junction boxes and longer wires. However I don’t see it mentioned but you can’t run Romex on the underside of a joist or in the case ridge beam. You . Now that you can get small, desktop CNC machines, it is more accessible than ever to make beautiful wood projects at home and sell them for a profit online. Below you will find some amazing CNC projects for beginners and more advanced woodworkers. All of them are top sellers on Etsy and at craft fairs around the country.
0 · attic splices nec
1 · attic splice box requirements
2 · attic splice box
A junction box is not a special type of box but any standard electrical box used to enclose wire splices. The most commonly used box for junctions is a 4-inch square box (either metal or strong plastic), which offers ample space for making wire connections with multiple wires or .
I am going to run a section of 12/2 romex from the first light's jbox to the second light's jbox. Do I need to staple the romex down to the ceiling joists in the attic space or can i just run the romex .If it's just a romex splice, adding a junction box is your easiest option. It's not hard .320.23 (A) Where run across the top of floor joists, or within 2.1 m (7 ft) of floor or floor joists across the face of rafters or studding, in attics and roof spaces that are accessible, the cable .As everyone mentioned you need junction boxes and longer wires. However I don’t see it mentioned but you can’t run Romex on the underside of a joist or in the case ridge beam. You .
What are the requirements of splicing romex in attics in the NEC. Is it required to be spliced in a box? Please state where it is located in the NEC. Install another junction box. Cut the cable a foot before that box (so that you have some extra cable to use inside the box). Add a new cable to .
You have a pre-existing run of romex wire and you want to pop a new outlet into. For example, in an unfinished basement or attic, you can see the romex, know the complete .If it's just a romex splice, adding a junction box is your easiest option. It's not hard and doesn't take long. I don't see why you'd need to redo the entire line unless there's more going on than just this splice
attic splices nec
Would like some opinion on this attic and NM cable installation. Should the cables be properly supported? Junction boxes laying loose on attic floor acceptable? Yes, it's done all the time for outside lights, receptacles, etc. As long as the Romex lands in a box attached to the building. You can't have Romex outdoors, even in conduit. But is allowed to terminate directly into a box. Check with a stud finder and see if any fire stop blocking in the wall. If you find horizontal blocking then either open up wall around it or run THWN wires in conduit on outside .
Romex in attic goes through top plate to wall below. Squirrels chewed through and it needs to be replaced, but I have no slack to pull up from the wall below. It's chewed to an inch of the hole.
Old wiring was romex,, armored cable, Al, knob and tube. The house has a L shape on second story attic . I previously just let the new Romex lay where is was and will dress the wires mostly to the outside walls then along those walls to the fuse box area below. someday a real electrician will pick up where I left off and install a circuit breaker.Yeah, I found all sorts of open splices in my attic. To your point they had not started a fire in 40+ years, but I still disconnected them and put them in boxes for my own peace of mind. They also now make open splice boxes for this very reason. They're expensive, but it would be a massive time save and really easy to install for a beginner.I ran into some strange electrical wiring in a junction box in my attic that doesn't make sense. There are two old style 2 wire (Black/White, no ground) wires and a newer romex with ground as well. I can't tell where the romex runs to as it feeds through the attic floor into a .Since I have attic access and since romex is not cheap, I am wondering if I can pigtail the garage door outlet at the top of the garage into a junction box in the attic, then use that same pigtail to connect 6 romex wires for the new outlets. This would prevent me from having to send 2 romex wires down to each outlet.
If I had to do what you're trying to do I would probably pull MC cable from the panel to the attic and then junction in a properly sized box like a 12x12 metal or similar. Or just do multiple 4x4 boxes with a couple circuits each.Hi - want to put junction box in unfinished attic attached to joist to turn existing 20amp (12 gauge yellow sheathed Romes) branch into two branches so I can drop a branch down for electric toilet bidet seat. Yes, GFCI protected. Junction box will only house the pigtails joining the two output branches with the input.Get the Reddit app Scan this QR code to download the app now . Believe it or not, it was actually helpful in determining where to route wires in my attic and unfinished basement . the carpenter and electrician collaborated to create a box inside the upper shelf space to house the junction box and cover the romex coming in from the stud wall.
Any and all splices need to be inside a junction box. The junction box must always remain accessible. Boxes are cheap af. Go to any hardware store and they're literally a dollar. They make a TYCO romex splice kit that some municipalities allow, but YMMV.I am looking to install a plug in my attic for a projector that has its power cord running up through a brush plate. My plan was to splice into one of the existing runs off a nearby circuit. I know the process of splicing Romex as far as installing a box to secure the wires for safety code.The existing light has a square metal j-box with 4 romex cables running into it: Line in, switch and feeding power into 2 other lights) The LED lights come with their own little junction box. The LED j-box is separate from the LED light - see the picture. The problem is that this little box cannot possibly handle all of those wires!
The new location is about 4 feet farther away and I need to extend the AC to reach it. My plan is to completely remove the old fan and extend the electrical supply through a junction box secured visibly on a roof truss to reach the new fan location. Does this meet code?
Put the box a foot over, bring the cable up through the top plate above the outlet, and then swing it over to the box, and there will be room to put a cable strap on it. If there are two outlets near each other, put the box half way between and run the drops over a few feet in the attic to save on another junction and splice to make.
If you just cut the romex then you won't have enough slack for the wires entering your jbox. If this wire is your only option then you would need to install a double jbox where you cut the wire in 2 places about 18" apart, install a box on each romex end so the boxes are about 6 inches apart, run a new romex between the new jboxes and then you can do your makeup to keep the .Just use the right ROMEX adapter in the box when running the wire in it. Dont just punch a hole out and stick ROMEX in it and wire up. Secure the wire so it doesnt rub through.The boxes are required by code for a reason. If, over years, the connection should become loose, it could arc, and spark. If its in a box, that's not goid, but not disastrous. If its not in a box, it could cause a house fire. Use a box, follow the code.
I've got a sloped roof, in a not-too-tall attic. Where the roof peaks, it's easily 6' tall. As the roof drops, it eventually gets as low as 2' tall. I've also got loads out near/at the soffit that I'd like to power, and that means splicing them into the Romex, and that means junction boxes. They'll be easily visible from the tall part of the .Put a large junction box in the attic. That way you can pull THHN wires through your conduit and transition to Romex as needed in the junction box. Much easier to run those individual wires in conduit especially if you end up with a few bends. Have them leave a .
attic splice box requirements
Welcome to /r/Electricians Reddit's International Electrical Worker Community aka The Great Reddit Council of Electricians Talk shop, show off pictures of your work, and ask code related questions. Help your fellow Redditors crack the electrical code.
Posted by u/yosterstrudle - 3 votes and 4 commentsIf I run the cable up from the floor and mount the junction box outside, how do I properly run the cable so Romex is not exposed? I have a 14/2 running across the floor joist to the other side of the house where I want to supply power to 3 outlets and a light fixture.I opened up the walls in my bathroom to replace the shower and found this junction box in the wall. I know it's a no-no to hide a junction box, but to make it better this is next to the shower mixing valve. The circuit is for the dryer. Apparently when a previous owner moved the laundry they left this gem for me.
Welcome to /r/Electricians Reddit's International Electrical Worker Community aka The Great Reddit Council of Electricians Talk shop, show off pictures of your work, and ask code related questions. . If so, I assume I can run romex to a J-box, and then junction in the outdoor wire? . The junction box is fine in the attic, but it still needs .Four 12/2 Romex going into the box, I think that I'll use the 2 gang! Thanks. . Rack-A-Tiers Open Splice Junction Box, One-Piece Junction Box for Repairing Open Splices, 5 Second Installation (Single) . Welcome to /r/Electricians Reddit's International Electrical Worker Community aka The Great Reddit Council of Electricians Talk shop, show .
Now to a bigger mystery.. This Romex cable from 2015 apparently goes nowhere. The non-contact voltage pin doesn't beep with the romex cable where I'm sitting. It beeps when I put it next to the cord for the attic light. It's almost like they were going to hook up the cable, but never finished the job. That's so weird.What’s the best/easiest way to secure romex running behind a finished wall? I’m installing a celling fan fixture and I have attic access, so everything above the ceiling is going smoothly, as is dropping the wiring behind the wall down to the switch. But what’s the best way to secure the romex above the new junction box?The power and network cables both come down from the attic. My network box has the power outlet knockout located on the bottom. In case there isn't clearance around or behind the box to run the romex, would it be ok to run it through the box itself? . Per the NEC, you can have ordinary electrical in the same junction box as communications .
yellow and gold metallic fabric
attic splice box
The deep and dramatic tones of black cabinets enhance the modern and sleek appearance of stainless steel, making the appliances stand out as elegant focal points in your kitchen. Furthermore, black is a versatile color that complements various design styles, from minimalist and industrial to classic and transitional, providing you with plenty .
romex junction box in attic reddit|attic splice box